Over SNMP communication, battery test can be started or current test can be cancelled. UPS can be shut-down or
stand-by (stand-by duration is adjustable). Alarms can be discarded.
If Serial Communication cable is needed, it can be produced according to the
pin configuration described at side.
8.2. Internal SNMP Communication
Internal SNMP card can be installed into SNMP slot placed at the front of UPS. As soon as SNMP installed, RS232 port
would be disabled.
Internal SNMP has the same features as External SNMP; refer to
Section 8.1 for more information.
SNMP JUMPER (J2 J3): If internal SNMP would
be used, 2 jumpers should be moved to upper
side.
If RS232 or RS485 would be used, 2 jumpers
should be moved to lower side.
If the jumpers are at the upper side for internal SNMP configuration, RS232 and RS485 Serial
Communication are disabled.
If the jumpers are at the lower side for RS232 or RS485 configuration, internal SNMP is disabled.
SNMP RS232 - RS485