Appendix-2: Modbus List
While reading data through MODBUS, the following addresses can be used. "03 - Read Holding Registers" must be
selected to read the MODBUS data.
We can send commands by using MODBUS. To do that function 06 Write Single Register must be used.
The data is defined as unsigned words (2 bytes).
Address Coefficient Data Definition Read (R) / Write (W)
100 1 L1 Input Voltage R
101 1 L2 Input Voltage R
102 1 L3 Input Voltage R
103 1
L1 Input Current
R
104 1
L2 Input Current
R
105 1
L3 Input Current
R
106 0,1 Input Frequency R
107 1 L1 Output Voltage R
108 1
L2 Output Voltage
R
109 1
L3 Output Voltage
R
110 1 L1 Output Current R
111 1
L2 Output Current
R
112 1
L3 Output Current
R
113 0,1 Output Frequency R
114 1 L1 Output Load Percentage R
115 1
L2 Output Load Percentage
R
116 1
L3 Output Load Percentage
R
117 1 L1 Bypass Voltage R
118 1
L2 Bypass Voltage
R
119 1
L3 Bypass Voltage
R
120 1 Positive Battery String Voltage R
121 1 Negative Battery String Voltage R
122 1 Positive Battery String Current R
123 1 Negative Battery String Current R
124 1 Battery / Ambient Temperature R
125 1 Positive DC Bus String Voltage R
126 1 Negative DC Bus String Voltage R
127 1 UPS Conditions and Alarms (***) R
201 1
If "1" is sent then beeper will be on. If "0" is sent then beeper
will be off.
R/W
202 1 If "1" is sent then a battery test will start. R/W