39
Appendix-2: Modbus List
While reading data through MODBUS, the following addresses can be used. "03 - Read Holding Registers" must be
selected to read the MODBUS data.
We can send commands by using MODBUS. To do that function 06 – Write Single Register must be used.
The data is defined as unsigned words (2 bytes).
Address Coefficient Data Definition Read (R) / Write (W)
100 1 L1 Input Voltage R
101 1 L2 Input Voltage R
102 1 L3 Input Voltage R
103 1
L1 Input Current
R
104 1
L2 Input Current
R
105 1
L3 Input Current
R
106 0,1 Input Frequency R
107 1 L1 Output Voltage R
108 1
L2 Output Voltage
R
109 1
L3 Output Voltage
R
110 1 L1 Output Current R
111 1
L2 Output Current
R
112 1
L3 Output Current
R
113 0,1 Output Frequency R
114 1 L1 Output Load Percentage R
115 1
L2 Output Load Percentage
R
116 1
L3 Output Load Percentage
R
117 1 L1 Bypass Voltage R
118 1
L2 Bypass Voltage
R
119 1
L3 Bypass Voltage
R
120 1 Positive Battery String Voltage R
121 1 Negative Battery String Voltage R
122 1 Positive Battery String Current R
123 1 Negative Battery String Current R
124 1 Battery / Ambient Temperature R
125 1 Positive DC Bus String Voltage R
126 1 Negative DC Bus String Voltage R
127 1 UPS Conditions and Alarms (***) R
201 1
If "1" is sent then beeper will be on. If "0" is sent then beeper
will be off.
R/W
202 1 If "1" is sent then a battery test will start. R/W